Release notes ACC MT Description: Air Center Control with Touch Display Software version: 2.0.1 Release date: April 2022 Hardware: 8 733 502 082 and 7 733 701 822 These release notes show an overview about the status of the software including limitations and known issues of ACC MT software version 2.0.0. Software Status --------------- Newly added features: - Hydrobox visible on system monitor and error manager - S-Box visible on system monitor and error manager - Simultaneously connecting a 2-pipe system (AF5300 series or MDCI) together with a 3-pipe system (AF6300 series) is now supported - ERV can now be controlled by ACC MT - AHU can now be controlled by ACC MT - USB update now available within installation wizard - Scanning is now more reliable - MDCI offers now all possibilites as AF5300. However, see limitations for MDCI below. Removed features: - None Improvements: - Several bugs fixed - Security patches - Improved robustness and performance for large systems > 64 IDUs - Improved robustness in combination with XYE Extension Kit - Scanning is now more reliable Limitations / known issues -------------------------- General: - To be able to select a country not yet existent in the pre-installed software version, this version must be already installed first. A factory reset is required after a software update to reach the installation wizard again to select the country. Group editor: - Although written differently in the manual, the group editor can only be access by an "Administrator" user. IDU listings: - Scrolling with a long list of IDUs: Use either scroll bar, or touch the white area left of the check boxes or right of the rename icon to scroll instead of drag-n-drop. Time and date settings: - 12-hour time format is only working for visualization of current time within dashboard and footer. All other functions are 24-hour time format only. Suggestion: Only use 24-hour time format. Fault and event history - In rare cases, already solved errors on IDU side still show as pending error within the fault and event history. If this is the case, please clear the fault and event history. MDCI: - General system limitation - Dry mode can be enabled on all controls (ACC MT, ARC and IRC) for IDUs connected to MDCI systems, but response to ACC MT is always cooling mode. This means, after some seconds, ACC MT will show cooling mode instead of dry mode. - Only mode and IRC lock are possible, although others like ARC lock are now offered by the ACC MT, those locks are non-functional in MDCI systems. - IDUs which are in mode conflict are shown as "off" on ACC MT. - ACC MT shows always the default icon "4-way cassette IDU", independent from the real IDU type. - The current outdoor temperature display is not available. - System structure: No outdoor unit information available. - System monitor: No diagnosis data available for MDCI systems. - Limitations depending on ODU firmware - Although the ACC offers seven fan speeds, those may be mapped to three fan speeds in case the ODU executes an old firmware (update not possible). Use of seven fan speeds via the ARC and IRC still possible. Contact ------- In case of facing abnormalities and limitations which are not recoverable by the resolutions offered in this document please contact your regional sales department.